Service Hotline

    020-38031777-8013

NH-1180 thick fire retardant coating

Application areas
Suitable for super high-rise steel structures, large-span steel structure plant, tunnel engineering, petrochemical engineering, but also for civil and general industrial plant roof and wall sound absorption, insulation and so on.
Product Features
Environmental protection, no harm to the human body;
Construction is simple, dry and fast curing;
Light coating, strong bond, high strength;
Fire-resistant, weathering performance is excellent;
Construction technology
Process
Technical specifications
The main material
Substrate processing
Clean the surface of steel components foreign body and rust, metal surface treatment of oil, to rust Standard ST2
 
Bottom
The thickness of the main ingredients of the binder and water in accordance with a certain proportion of mixing evenly, brushing or spraying the surface of the substrate 1-2 times, the table can be dry for the next construction
NH-1180 thick fire retardant coating
Fire paint construction
The use of spraying equipment construction, each spraying thickness of 5-10mm, separated by 12-24 hours spray again, until the required thickness so far, Bureau of repair can be hand-painted.
NH-1180 thick fire retardant coating
Putty construction
Wipe the putty on the thick coating surface, dry and polish smoothly
Other brands of putty
Topcoat construction
In a smooth putty layer, spray 1-2 times strong weathering oily topcoat for protection or decoration thick paint
Lanling / Rolls polyurethane finish

  note:
Construction Conditions:
1, the temperature is below 5 ℃, relative humidity greater than 90%, the wind speed is greater than 5m / s or rainy days and steel structure surface dew condensation should not be construction;
2, paint the construction interval should be controlled at 12 ~ 24h (temperature at 20 ℃), not too long or too short, the general winter may be appropriate to extend the summer is appropriate to shorten. When the weather is hot or extremely dry, it is necessary to create the necessary curing conditions (plastic film cover, surface brushing water, etc.), otherwise it will affect the binding force of paint layer and easily cause hollowing, falling off and powdering;

Technical Parameters
Test items
Technical indicators
The status in the container
After mixing was fine and delicate state, no caking
Drying time (dry table) / h
≤24
Initial dry crack resistance
1-3 cracks are allowed, the width should be ≤ 1 mm
Bond strength / MPa
≥0.04
Compressive strength / MPa
≥0.03
Dry density / (kg / m³)
≤500
Water resistance / h
≥24 coating should be no layer, foam, off phenomenon
Resistance to heat cycle / time
≥15 coating should be no cracking, peeling, foaming phenomenon
Fire resistance
Coating thickness / mm (not more than)
25 ± 2
Fire resistance / h (not less than) (made of I-beam made of 136b or 140b standard)
2.0